dc.description | Kabel merupakan elemen yang penting dalam menghantarkan arus listrik. Di
dalam instalasi listrik gedung, kabel berperan sangat penting. Hal ini dikarenakan
dalam pemilihan kabel tidak boleh sembarang dilakukan. Di samping itu
pengaman juga berperan penting karena pengaman adalah suatu peralatan listrik
yang digunakan untuk melindungi pengguna instalasi listrik maupun komponen
instalasi listrik dari kerusakan atau bahaya yang diakibatkan oleh gangguan
seperti arus beban lebih atau arus hubung singkat. Penelitian ini bertujuan agar
diketahui data yang akurat tentang penghantar (kabel) dan circuit breaker
(pengaman) agar tepat dan sesuai dengan kebutuhan beban gedung admisi
Universitas Muhammadiyah Yogyakarta serta standar yang telah ditentukan. Dari
hasil perhitungan, kabel yang digunakan antara lain NYY 4x6 mm2 dengan KHA
43 A, NYY 4x10 mm2 dengan KHA 60 A, NYY 2x6 mm2 dengan KHA 43 A dan
NYY 4x50 mm2 dengan KHA 174 A berdasarkan PUIL 2000. Drop tegangan
didapatkan hasil berkisar 0,02-0,76 %, sehingga aman sesuai standar PUIL 2000
dan SPLN 1978 karena tidak lebih dari 5 %. MCCB dan nilai breaking capacity
sesuai standaryaitu 20 A dan 40 A. | en_US |
dc.description.abstract | Cable is an important element in conducting electrical current. In building
electrical installations, cables play a very important role. This is because in the
selection of cables should not be done. In addition, the safeguard also plays an
important role because the safeguard is an electrical equipment used to protect
the user's electrical installation and electrical installation components from
damage or danger caused by interference such as overload current or short
circuit current. This study aims to know the accurate data about the conductor
(cable) and circuit breaker (safety) to be precise and in accordance with the needs
of building admissions Universitas Muhammadiyah Yogyakarta and the standards
that have been determined. From the calculation, cable used is NYY 4x6 mm2 with
KHA 43 A, NYY 4x10 mm2 with KHA 60 A, NYY 2x6 mm2 with KHA 43 A and NYY
4x50 mm2 with KHA 174 A based on PUIL 2000. Drop voltage got result of 0 ,
02-0.76%, so it is safe according to PUIL 2000 and SPLN 1978 standards for no
more than 5%. MCCB and breaking capacity value according to the standard ie
20 A and 40 A. | en_US |
dc.subject | Strong Conductivity of Current, Drop Voltage, Breaking Capacity Kuat Hantar Arus, Drop Tegangan, Breaking Capacity | en_US |
dc.title | ANALISIS PENGHANTAR DAN PENGAMAN PADA GEDUNG ADMISI UNIVERSITAS MUHAMMADIYAH YOGYAKARTA | en_US |
dc.type | Thesis
SKR
F T
054 | en_US |