dc.description | Rumah sakit Islam Muhammadiyah Kendal merupakan amal usaha yang memiliki tugas dalam memberikan pelayanan kesehatan. Dalam upaya memenuhi pelayaan yang baik, rumah sakit ini memiliki dua buah transformator distribusi 20kV dengan kapasitas maksimum masing-masing sebesar 197kVA. Hampir seluruh peralatan listrik yang terpasang merupakan peralatan dengan beban non linier.
Penelitian ini menganalisis mengenai kualitas daya listrik yang mencakup faktor daya, haromisa dan ketidakseimbangan beban dengan menggunakan alat power quality analyzer MI metrel 2892 , sehingga dapat di ketahui nilai daya listrik pada rumah sakit.
Berdasarkan hasil pengukuran pada panel MDP satu diperoleh hasil 5,84% – 12.59% yang telah memenuhi standar IEEE 519-1992 sedangkan pada panel MDP dua diperoleh nilai THDI sebesar 6,08% – 20.29% yang telah melebihi standar yang ditentukan. Losses yang ditimbulkan oleh harmonisa yaitu sebesar 0,834 kW. Pada ketidakseimbangan arus diperoleh nilai 32%. Hal ini telah melebihi standar ANSI C84. 1-1995 yaitu sebesar 20% sehingga berdampak pada timbulnya arus netral. | en_US |
dc.description.abstract | Muhammadiyah Kendal Islamic Hospital is a business charity that has the task of providing health services. In an effort to fulfill good service, the hospital has two 20kV distribution transformers with a maximum capacity of 197kVA. Almost all installed electrical equipment are equipment with non-linear loads.
This study analyzes the quality of electric power which includes power factor, haromisa and load imbalance using the MI metrel 2892 power quality analyzer, so that the value of electrical power in the hospital can be known.
Based on the measurement results in the MDP panel one obtained results 5,84% – 12.59% that had met the IEEE 519-1992 standard while in the MDP panel two THDI values were obtained from 6.08% - 20.29% which had exceeded the specified standard. Losses caused by harmonics are equal to 0.834 kW. In the current imbalance obtained a value of 32%. This has exceeded the ANSI C84 standard. 1-1995 which is equal to 20% so that it has an impact on the emergence of neutral currents | en_US |
dc.publisher | FAKULTAS TEKNIK UNIVERSITAS MUHAMMADIYAH YOGYAKARTA | en_US |
dc.subject | harmonics, load unbalance, power factor, power quality analyzer | en_US |
dc.title | AUDIT ENERGI PADA SISTEM KELISTRIKAN RUMAH SAKIT ISLAM MUHAMMADIYAH KENDAL | en_US |