dc.description | Penelitian ini dilaksanakan bertujuan untuk mendapatkan informasi tentang
hambatan pentanahan kaki tower Saluran Udara Tegangan Tinggi SUTT) di Gardu
Induk Bantul saluran transmisi Bantul – Wates pada tahun 2015 sampai dengan tahun
2019. Pengukuran nilai hambatan menggunakan alat Earth Tester, pengukuran
dilakukan pada 20 buah tower yang dilaksanakan PT. PLN (Persero) P3B-JB REGION
JATENG DAN DIY Unit Pelayanan Transmisi (UPT) Bantul 150 KV. Hambatan kaki
yang rendah berguna sebagai jalan pintas untuk meredam arus sambaran petir,
hambatan kaki pada tower transmisi yang ditetapkan kurang dari 10 ohm. Hambatan
yang melebihi nilai ini tidak terjamin keamanan proteksi saluran transmisi udara, back
flashover sangat berpeluang terjadi pada keadaan ini. Kondisi hambatan pentanahan
tower SUTT 150 KV transmisi Bantul - Wates pada tahun 2016 paling buruk/bahaya
yaitu dengan jumlah tower 10 dengan kondisi baik, 2 tower dengan kondisi
sedang/awas dan 8 tower dengan kondisi buruk/bahaya dibandingkan kondisi
hambatan pentanahan tower SUTT 150 KV transmisi Bantul - Wates pada tahun 2015,
2017, 2018 dan 2019. Kondisi hambatan pentanahan tower SUTT 150 KV transmisi
Bantul - Wates paling baik adalah pada tahun 2015 yaitu dengan 13 tower dengan
kondisi baik, 4 tower dengan kondisi sedang/awas, 3 tower dengan kondisi
buruk/bahaya. | en_US |
dc.description.abstract | This research was carried out aimed at obtaining information about the barriers to
grounding the SUTT High Voltage Air Channel tower) at the Bantul Substation Bantul-
Wates transmission line in 2015 until 2019. Measuring the resistance value using the
Earth Tester tool, measurements were carried out on 20 towers carried out by PT. PLN
(Persero) P3B-JB Central Java and DIY Transmission Service Unit (UPT) Bantul 150
KV. Low leg resistance is useful as a shortcut to reduce the current of lightning strikes,
the leg resistance on the transmission tower is set to be less than 10 ohms. Obstacles
that exceed this value are not guaranteed to protect air transmission lines, back
flashovers are very likely to occur in this situation. The obstacle condition in the
grounding of the SUTT 150 KV tower transmission in Bantul-Wates in 2016 was the
worst / danger, namely with the number of tower 10 in good condition, 2 towers with
medium / high condition and 8 towers with bad / hazard conditions compared to the
obstacle conditions for grounding the SUTT 150 KV tower the transmission of Bantul
- Wates in 2015, 2017, 2018 and 2019. The best conditions for the grounding of the
SUTT 150 KV transmission transmission tower in Bantul - Wates are in 2015, with 13
towers in good condition, 4 towers with moderate conditions, 3 towers with bad /
dangerous conditions | en_US |
dc.publisher | FAKULTAS TEKNIK UNIVERSITAS MUHAMMADIYAH YOGYAKARTA | en_US |
dc.subject | Value of Obstacles, Tower, Grounding | en_US |
dc.title | ANALISIS NILAI HAMBATAN PENTANAHAN KAKI TOWER SALURAN UDARA TEGANGAN TINGGI (SUTT) 150 KV BANTUL - WATES | en_US |
dc.type | Thesis