      ANALISIS LOSSES DAN DERATING AKIBAT PENGARUH THD (TOTAL HARMONIC DISTORTION) PADA TRANSFORMATOR DISTRIBUSI DI FAKULTAS TEKNIK (F1, F3, F4, G5, DAN G6) UNIVERSITAS MUHAMMADIYAH YOGYAKARTA

      Thumbnail
      View/Open
      COVER (215.3Kb)
      HALAMAN JUDUL (408.2Kb)
      HALAMAN PENGESAHAN (384.3Kb)
      HALAMAN PENGESAHAN (357.7Kb)
      BAB I (344.0Kb)
      BAB II (809.7Kb)
      BAB III (283.1Kb)
      BAB IV (1.138Mb)
      BAB V (261.7Kb)
      DAFTAR PUSTAKA (214.4Kb)
      LAMPIRAN (1.327Mb)
      LAMPIRAN (161.9Kb)
      Date
      2017-04-22
      Author
      ADILIN, RADEN SAIFUL GHAZI
      Metadata
      Show full item record
      Abstract
      High level of harmonics is very influential on the transformer, and the transformer performance parameters are determined through loss - power losses that occur on the transformer and a decrease in working capacity (derating) which may occur as a result of the harmonic distortion. In this research, analysis of THD (Total Harmonic Distortion) measurement and simulation results with the IEEE 519-1992, analysis of losses in the transformer after affected harmonics, derating analysis that occurs on the transformer, as well as the analysis of additional losses due to current THD. The analysis showed that the value of the voltage across each phase THD Sub Distribution Panel, THD voltage has a value that meets the standard, current THD measurement results mostly not meet the standards. Results of analysis of losses due to harmonics of 2.25 kW/day. Derating that occurs in the transformer is equal to 403.24 kW.
      URI
      http://repository.umy.ac.id/handle/123456789/10259
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV