      ANALISIS KEANDALAN SISTEM DISTRIBUSI 20 KV DI PT. PLN (PERSERO) RAYON MARTAPURA SELAMA TAHUN 2017

      Thumbnail
      View/Open
      COVER (220.0Kb)
      HALAMAN JUDUL (1.660Mb)
      HALAMAN PENGESAHAN (629.2Kb)
      INTISARI DAN ABSTRAK (178.8Kb)
      BAB I (309.6Kb)
      BAB II (909.8Kb)
      BAB III (241.9Kb)
      BAB IV (875.5Kb)
      BAB V (182.6Kb)
      DAFTAR PUSTAKA (293.4Kb)
      LAMPIRAN (841.8Kb)
      NASKAH PUBLIKASI (524.9Kb)
      Date
      2018-08-15
      Author
      NURFAUZY, MUHAMMAD FAISHAL
      Metadata
      Show full item record
      Abstract
      Reliability of a distribution system is a factor that is very influential on the continuity of electrical energy distribution to customers. This study aims to determine the reliability of the distribution system of each feeder at PT. PLN (Persero) Rayon Martapura through the calculation of the SAIFI index, and SAIDI based on monitoring data of power outages that occurred during 2017. The method used in this study is to calculate the value of the SAIFI index, and SAIDI on each feeder at Rayon Martapura then compare it to the SPLN standard No. 68-2 1986, IEEE Std 1366-2003, and the working target standard of Rayon Martapura in 2017. Based on the analysis, it is found that in 2017 the distribution system of Rayon Martapura is categorized reliably because each feeder has a range of SAIFI values, and SAIDI has fulfilled the rayon work target. However, when reviewed from the SPLN standard no. 68-2 1986 then the value of SAIFI, and SAIDI that meet the standards only on CPK 01, while another feeder has not met the standard. In addition, if reviewed from the IEEE standard std 1366-2003 then the value of SAIFI, and SAIDI all feeders on Rayon Martapura not meet the standards.
      URI
      http://repository.umy.ac.id/handle/123456789/21096
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV