      ANALISIS SISTEM PENTANAHAN GEDUNG K.H IBRAHIM (TWIN BUILDING) E6,E7 UNIVERSITAS MUHAMMADIYAH YOGYAKARTA

      Thumbnail
      View/Open
      COVER (76.26Kb)
      HALAMAN JUDUL (596.0Kb)
      HALAMAN PENGESAHAN (3.397Mb)
      ABSTRAK (138.2Kb)
      BAB I (48.58Kb)
      BAB II (509.7Kb)
      BAB III (113.4Kb)
      BAB IV (963.5Kb)
      BAB V (88.59Kb)
      DAFTAR PUSTAKA (38.70Kb)
      NASKAH PUBLIKASI (345.4Kb)
      Date
      2019-05-20
      Author
      FEBRIAN, DENY
      Metadata
      Show full item record
      Abstract
      The grounding system has a purpose, as the safety of buildings from hazards due to lightning strikes, installation failures that are analyzed and compared to the PUIL standard, PUIPP, Minister of Manpower Regulation on 1989 concerning lightning, SNI, IEEE, and IEC suppliers.This study using the methodology of comparing the value of building detainees in the form of schematic drawings and actual conditions in the field and then analyzed and concluded based on standards. Supporting data is obtained from references to books and journals related to grounding systems.KH Ibrahim building requires high lightning protection where KH Ibrahim building is in category III, the diameter of KH Ibrahim's lightning protection building is 57.4 m2, the protective surface area is 1.42 km2 and the lightning protection failure rate is 0.30% . Grounding resistance is 2.38 Ω for lightning rods while planning for soil resistance is 1.19 Ω. Grounding resistance on E6 building electrical is 2.38 Ω and E7 building is 0.56 Ω. Therefore K.H Ibrahim building grounding system meets the standards which explain the grounding system must be under 5 Ω for grounding systems.
      URI
      http://repository.umy.ac.id/handle/123456789/27832
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV