      ANALISIS PENGUJIAN TAHANAN ISOLASI TANGENT DELTA BUSHING GENERATOR TRANSFORMER PT. INDONESIA POWER UJP PLTU JAWA TENGAH 2 ADIPALA

      Thumbnail
      View/Open
      COVER (51.33Kb)
      HALAMAN JUDUL (404.4Kb)
      HALAMAN PENGESAHAN (411.4Kb)
      ABSTRAK (34.32Kb)
      BAB I (43.72Kb)
      BAB II (607.3Kb)
      BAB III (138.5Kb)
      BAB IV (307.0Kb)
      BAB V (37.28Kb)
      DAFTAR PUSTAKA (143.9Kb)
      LAMPIRAN (1.203Mb)
      NASKAH PUBLIKASI (409Kb)
      Date
      2019-07-20
      Author
      ARROSYID, MUHAMMAD FATHUL AMIN
      Metadata
      Show full item record
      Abstract
      In this study conducted testing to know the isolation prisoners on the generator bushing transformer PT. INDOENSIA POWER UJP PLTU Jawa Tengah 2 Adipala is still in good condition after the flashover. In this study the way to know the insulation resistance is still in good condition is to collect data and do testing the tangent delta at the research site. Further analyze whether the test results gained are well worth in accordance with the ANSI C 57.12.90 standards. In this study came the result that the testing of the tangent delta isolation prisoner on the transformer's generator bushing after the flashover was poorly priced under the standard. This is because of contamination in the isolation of bushing so that action is performed to get the best value of tangent delta. After the action is obtained the result of tangent delta with a value of 0.4984% for phase R, 0.4412% for phase S, and 0.4131% for phase T, where the value meets ANSI C standard 57.12.90 so that the equipment can work properly.
      URI
      http://repository.umy.ac.id/handle/123456789/29009
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV