      AUDIT ENERGI DAN ANALISIS KUALITAS DAYA LISTRIK DI RUMAH SAKIT GIGI DAN MULUT ASRI MEDICAL CENTER YOGYAKARTA

      Thumbnail
      View/Open
      COVER (88.51Kb)
      HALAMAN JUDUL (1.630Mb)
      HALAMAN PENGESAHAN (1014.Kb)
      ABSTRAK (134.0Kb)
      BAB I (78.83Kb)
      BAB II (366Kb)
      BAB III (232.2Kb)
      BAB IV (949.3Kb)
      BAB V (188.8Kb)
      DAFTAR PUSTAKA (66.50Kb)
      LAMPIRAN (1.367Mb)
      NASKAH PUBLIKASI (463.8Kb)
      Date
      2019-03-23
      Author
      ALFIYANSYAH, MAHENDRA
      Metadata
      Show full item record
      Abstract
      Non-linear loads are one of the important factors that affect the quality of electricity for consumers. This load is a harmonic source which can reduce the quality of electric power. Non-linear load is generally a semiconductor component, where this load requires a non-fixed current in the period of increase. Examples are AC drives, DC drives, Static Converter and so on. Therefore the author chose the title "Audit and Analysis of Electric Power Quality in the AMC Yogyakarta Dental and Oral Hospital", with the aim of being able to carry out an analysis of electrical power quality, calculate power losses to produce harmonics and imbalances, and provide solutions to reduce harmonics. From the calculations that have been done, it can be seen that the cost-loss from harmonics and imbalance is Rp. 1,039,689/year. From the measurements and calculations performed can be calculated the maximum harmonic value measured in the Main Distribution Panel (MDP), which is worth 22% measured in the 3rd order
      URI
      http://repository.umy.ac.id/handle/123456789/29046
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV