      ANALISIS THERMOVISI UNTUK MENEMUKAN HOT POINT PADA GARDU INDUK 150 KV PEDAN BERBASISKAN PEMROGRAMAN C#

      Thumbnail
      View/Open
      COVER (240.0Kb)
      HALAMAN JUDUL (792.5Kb)
      HALAMAN PENGESAHAN (659.6Kb)
      ABSTRAK (181.0Kb)
      BAB I (399.4Kb)
      BAB II (1.383Mb)
      BAB III (424.5Kb)
      BAB IV (1.044Mb)
      BAB V (190.5Kb)
      DAFTAR PUSTAKA (392.5Kb)
      LAMPIRAN (924.6Kb)
      NASKAH PUBLIKASI (739.4Kb)
      Date
      2019-03-29
      Author
      KURBANA, AKBAR
      Metadata
      Show full item record
      Abstract
      Thermovisi is an instrument used to visualize and detect the hot spots contained in an object using infrared technology. Thermovisi is useful for knowing the condition of the equipment contained in the switchyard. Temperature measurement on an object also has a weakness in obtaining the actual temperature of an object being measured. This is because the emissivity value of an object varies from 0 to 1. The heat temperature on substation equipment is a parameter that is seen and analyzed changes every time. This is related to system reliability and protection at the substation. This final project discusses the validation method to test that the measurements made are accurate and precise by using manual calculations and using Microsoft Visual Studio C # software according to the parameters used. The results obtained are 68 connections on the terminal in good condition, 5 connections at the terminal under conditions of maintenance checks and 1 connection at the terminal under immediate repair conditions. For the emissivity of the equipment at the substation using 1 type of material, the emissivity value varies due to several factors, with the accuracy of each transformer bay 1 to transformer bay 3 being 97.44%, 95%, 99.97% . And for the precision value of 0.61%, 1.43%, 0.58%, respectively. The results of the measurements are stated to be accurate and precise so that the calculation validation test method can be used.
      URI
      http://repository.umy.ac.id/handle/123456789/29072
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV