      ANALISIS THERMOVISI UNTUK MENEMUKAN HOT POINT PADA GARDU INDUK 150 KV KENTUNGAN BERBASISKAN PEMROGRAMAN MATLAB

      Thumbnail
      View/Open
      COVER (310.4Kb)
      HALAMAN JUDUL (500.1Kb)
      HALAMAN PENGESAHAN (524.1Kb)
      ABSTRAK (267.9Kb)
      BAB I (429.5Kb)
      BAB II (982.8Kb)
      BAB III (502.8Kb)
      BAB IV (1.301Mb)
      BAB V (408.6Kb)
      DAFTAR PUSTAKA (314.0Kb)
      LAMPIRAN (763.9Kb)
      NASKAH PUBLIKASI (554.5Kb)
      Date
      2019-10-17
      Author
      PAMBUDI, RESTU AJI RILO
      Metadata
      Show full item record
      Abstract
      Measurement using thermovision is part of the maintenance performed on substation equipment. Thermovision has functions to visualize and detect hot points in equipment. Thermovision work using infrared technology. Measurement using thermovision also has a weakness to find the actual temperature. This is because the emisvity value of the measured object varies between 0 to 1. This thesis discusses the validation method to test that the measurements made are accurate and precise using manual calculations and using Matlab software. Research focuses on the transformer clamp and conductors. From 66 connections, 62 connections at the terminal were in good condition and 4 connections at the terminal were in inspection while maintenance. The value of emissivity in the substation equipment is differend even though it uses 1 type of material because some factors, with an accuracy about 96.98% at transformer bay 2 , 96.44% at transformer bay 3 and 95.36% at transformer bay 4 . And the precision value is 1.98% at transformer bay 2, 1.05% at transformer bay 3 and 1.75% at transformer bay 4. The results show good accuracy and precision value, so the calculation validation test method can be used.
      URI
      http://repository.umy.ac.id/handle/123456789/30281
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV