ANALISIS KEANDALAN DISTRIBUSI TENAGA LISTRIK BERDASARKAN INDEKS SAIFI, SAIDI, DAN CAIDI DI GARDU INDUK WATES
Abstract
One of the most important factors of operating a network system is reliability. there are several things that are important parameters in determining an reliability index of a system of distribution, namely SAIFI, SAIDI, and CAIDI, these three aspects are important parameters for determining reliability in an electric power distribution system in a substation.
This research aims to find out how much the level of reliability possessed by the distribution system at the Wates Substation, by using the SAIDI, SAIFI, and CAIDI reliability indices and comparing them with SPLN, IEEE, and WCS and comparing them with graphs from matlab by entering values on the x and y axis. knowing this reliability can be a reference in order to improve the quality of service in the coming year.
Based on the results of calculations and analyzes that have been carried out, it can be said that the distribution system at the Wates substation can be said to be reliable, because almost all feeders meet the standards set by SPLN, IEEE, and WCS, although WT 05 feeders do not meet the standards for value. The WT 05 feeder for the SAIDI value has passed the standard value of WCS which is equal to 1.666 (hcyr) while the result obtained is 2.00 (hcyr). For WT 05 feeders, they have not met the standard for SAIFI values, they have passed the IEEE standard of 1.45 (tcyr) while the results obtained from the calculation are 2.21 (tcyr). For CAIDI scores there were 3 feeders who passed the IEEE 1.47 standard (hour / disturbance), WT 01 feeder at 1.84 (hour / disturbance), WT 04 feeder at 1.69 (hour / disturbance), and WT 06 feeder at 1.79 (hour / disturbance).