ANALISIS PRAKIRAAN KEMAMPUAN TRANSFORMATOR TERHADAP PERTUMBUHAN BEBAN PADA GARDU INDUK 150 kV GEJAYAN
Abstract
Basically, the basic needs of human beings in this world are vary. In the
past few years, the electricity needs of human beings in every year are increasing
so that for the digital era like today, electrical energy also become one of the
basic needs of mankind. In increasing the need of electrical energy, the load that
is supplied by transformer will continue to increase, and it will affect the ability of
150 kV Gejayan transformer in supplying the load. Analysed using multiple linear
regression methods, transformer 1 can only supply the optimal load for 4 years
only from 2014 to 2018, and transformer 1 supplies load with heavy load
condition with percentage Over 80% to 2033. While Transformer 2 is able to
supply optimal load longer, which is for 14 years from year 2014 to 2028. The
rest until the year 2033 already experienced a heavy load condition where the
loading percentage has exceeded the number of 80%.