PENGARUH HARMONISA TERHADAP KUALITAS DAYA LISTRIK DI GEDUNG E6 UNIVERSITAS MUHAMMADYAH YOGYAKARTA
Abstract
This study aims to efficiently electrical energy in the Muhammadiyah
University of Yogyakarta building by auditing all electrical quantities such as
voltage, current, frequency, harmonics, load imbalance and power loses by using the
Metrel 2892 gauge while the measurement time is 15 minutes for 24 hours during
office hours in the MVDP panel of UMY E6 Building. This study uses the standard
limits SPLN D5.004-1: 2012, the results of electrical energy audit research Building
E 6 get the results that the voltage harmonics of each phase of R 2.08%, S 2.72%, T
2.62% within the standard threshold SPLN D5.004-1: 2012. While the current
harmonics have an imbalance of R 12.31%, S 12.40%, and T 13.33% are still within
the threshold of SPLN D5.004-1: 2012. The amount of the harmonics affects the 3rd
and 5th order harmonics which have a total power loses of 24.41 Watt / minute