      ANALISIS PROFIL TEGANGAN DAN ARUS PADA GEDUNG LAYANAN KESEHATAN RSPAU Dr. S HARDJOLUKITO YOGYAKARTA

      Thumbnail
      View/Open
      COVER (453.7Kb)
      HALAMAN JUDUL (11.04Mb)
      HALAMAN PENGESAHAN (6.629Mb)
      ABSTRAK (399.7Kb)
      BAB I (353.3Kb)
      BAB II (810.4Kb)
      BAB III (345.5Kb)
      BAB IV (1.333Mb)
      BAB V (521.3Kb)
      DAFTAR PUSTAKA (344.5Kb)
      LAMPIRAN (587.2Kb)
      NASKAH PUBLIKASI (1.074Mb)
      Date
      2019-07-30
      Author
      SAPUTRA, GAGA HANDIKA REVANGGA
      Metadata
      Show full item record
      Abstract
      The electric power system used in Indonesia as a whole is a three phase voltage system with alternating current. This three-phase electrical energy is generated by a three-phase generator delivered through a three-phase transmission channel. In the process of ignition electrical energy from the center of the plant to the consumer must experience the drop voltage. The three phase electrical voltage system of the R phase, the S phase, and the T phase have to be balanced, if unbalanced it will occur in the neutral conductance. The use of nonlinear load causes the Terdistorsinya of sinusoida waves so as to cause harmonics. Due to load and harmonic imbalance caused the inefficiency of electrical energy use. The research was performed to determine the quality of electrical power in the RSAPAU of Dr. S Hardjolukito Yogyakarta. Measurements are done on LVMDP panel. The measurement is done for 24 hours with 30 minutes intervals. Measurements include frequency [Hz], voltage [volt], Total harmonic distortion (THD) voltage [%], current [ampere], Total Harmonic Distortion (THD) current [%], power factor, unbalance voltage [%], and unbalance current [%]. The result of electrical power quality measurement is known that there is a problem with total harmonic distortion (THD) current value [%] has crossed the IEEE 519-1992 standard limit of 12%. Harmonic currents cause the lack of efficiency of electrical energy consumption so as to pay a loss of Rp. 292,737 / year. Based on the results of the research and data analysis, to reduce harmonics done planning installation of passive Filter single tuned and active filter harmonics.
      URI
      http://repository.umy.ac.id/handle/123456789/30047
      Collections
      • Department of Electrical Engineering

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV
       

       

      Browse

      All of UMY RepositoryCollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

      My Account

      Login

      DSpace software copyright © 2002-2015  DuraSpace
      Contact Us | Send Feedback
      Theme by 
      @mire NV